Description
The Weintek HMI to Delta PLC MT-DVP communication cable is used to establish a serial communication link between Weintek Human Machine Interfaces (HMIs) and Delta PLCs (e.g., DVP-SS, SA, SC, ES2, EH3, etc.). This cable enables data exchange for monitoring and controlling PLC processes via the HMI. Below are key details:
Key Features
-
Compatibility:
-
Weintek HMIs: Compatible with most models (e.g., MT8000, MT6000, cMT series).
-
Delta PLCs: Works with DVP series PLCs (e.g., DVP-SS, SA, SC, ES2, EH3) that support RS-485 communication.
-
-
Interface:
-
HMI Side: Typically uses a 9-pin RS-232 or RS-485 port (depending on the HMI model).
-
PLC Side: Connects to Delta PLC’s 8-pin mini-DIN RS-485 programming port.
-
Cable Type: Acts as an RS-232/RS-485 converter to bridge the HMI and PLC protocols.
-
-
Communication Protocol:
-
Uses Modbus RTU or Delta’s proprietary protocol (configured in the HMI software).
-
Baud rates: 9600, 19200, 38400, etc. (must match PLC and HMI settings).
-
-
Wiring Configuration:
-
HMI (RS-485):
-
TX+ (Data+): Connects to PLC RS-485+ (Pin 6).
-
TX- (Data-): Connects to PLC RS-485- (Pin 5).
-
GND: Optional shielding (Pin 9 on HMI to PLC Pin 3).
-
-
Delta PLC 8-pin mini-DIN:
-
Pin 5: RS-485- (B)
-
Pin 6: RS-485+ (A)
-
Pin 3: GND (optional).
-
-
-
Software Setup:
-
Weintek HMI: Configure communication settings in EasyBuilder Pro:
-
Driver: Delta PLC DVP Series (Modbus RTU).
-
Port type: RS-485 2-wire.
-
Baud rate, parity, data bits (match PLC settings).
-
-
Delta PLC: Ensure PLC communication parameters align with the HMI (set via programming software like ISPSoft).
-
Typical Applications
-
Real-time data monitoring (e.g., sensor values, status bits).
-
Control of PLC outputs (e.g., buttons, switches via HMI).
-
Alarm management and historical data logging.
Setup Steps
-
Hardware Connection:
-
Connect the HMI’s RS-485 port to the Delta PLC’s 8-pin mini-DIN port using the MT-DVP cable.
-
Verify wiring polarity (A+/B- or TX+/TX-).
-
-
Software Configuration:
-
On the HMI:
-
Select Delta DVP (Modbus RTU) as the PLC driver.
-
Set the correct COM port, baud rate, station number (PLC address).
-
-
On the PLC:
-
Use Delta software (e.g., ISPSoft) to configure the PLC’s communication parameters (baud rate, parity, etc.).
-
-
-
Testing:
-
Use the HMI’s “Communication Test” tool to verify connectivity.
-
Monitor PLC registers (e.g., D, M, Y addresses) on the HMI.
-
Troubleshooting Tips
-
No Communication:
-
Check wiring polarity (swap A+/B- if necessary).
-
Ensure matching baud rates and parity settings.
-
Verify the PLC station address in the HMI configuration.
-
-
Intermittent Data:
-
Add a 120Ω termination resistor on the RS-485 line (if long-distance).
-
Shield the cable and ground the shield at one end.
-
Alternatives
-
Ethernet Communication: Use a Delta DVP-EN01 Ethernet module with Weintek HMI (for faster, long-distance communication).
-
USB-to-RS-485 Adapters: If the HMI lacks RS-485 ports.